  1. Summary of work

    A. Design, supply and install a complete clean agent total flooding fire suppression system using Novec 1230 Fire Protection Fluid (hereafter referred to as SYSTEM) which meets all the performance criteria described herein.
  2. Clean Agent Fire Suppression Fluid

    A. Clean agent fire suppression fluid shall be 3M Novec 1230 Fire Protection Fluid.

    B. Clean Agent Fluid shall have an Ozone Depletion Potential (ODP) of zero. ODP as defined by the US EPA.

    C. Clean Agent Fluid shall have a Global Warming Potential (GWP) of < 1 (100 year ITH). GWP as defined by the intergovernmental Panel on Climate Change Fifth Assessment Report (IPCC AR5) or in U.S. EPA documentation and approvals.

    D. Clean Agent Fluid shall not be one of these greenhouse gases or ozone depleters; Perfluorocarbons (PFCs), Hydrofluorocarbons (HFCs), and Hydrochlorofluorocarbons (HCFCs).

    E. Clean Agent Fluid must have a minimum safety factor 60% between the design concentration percentage and the No Observed Adverse Effect Level (NOAEL) for Class A and C hazards. For guidance on safety factors for Class B hazards, contact an approved Original Equipment Manufacturer.

    Download Complete Novec™ 1230 Specification Example (Word, 507 KB)

Non-Branded: Clean Agent Fire Suppression Fluid
Purple icon of fire suppression system nozzle

Copy and paste the following text into your specification or download the full specification example.

  1. Summary of work

    A. Design, supply and install a complete clean agent total flooding fire suppression system using agent manufactured by a reputable manufacturer with a process known as electrochemical fluorination. (Hereafter referred to as SYSTEM)

  2. Clean Agent Fire Suppression Fluid

    A. Agent shall be manufactured at an ISO 9001 and ISO 14001 registered facility.

    B. Clean Agent shall have an Ozone Depletion Potential (ODP) of zero. ODP as defined by the US EPA.

    C. Clean Agent shall have a Global Warming Potential (GWP) of < 1 (100 year ITH). GWP as defined by the Intergovernmental Panel on Climate Change Fifth Assessment Report (IPCC AR5) or in US EPA documentation and approvals.

    D. Clean Agent shall not be one of these greenhouse gases or ozone depleters; Perfluorocarbons (PFCs), Hydrofluorocarbons (HFCs), and Hydrochlorofluorcarbons (HCFCs).

    E. Agent will not be restricted for use in fire protection due to its Ozone Depletion Potential (ODP) or Global Warming Potential (GWP) and is not targeted for phase-down by the Montreal Protocol, nor subject to the European F-Gas Regulations targeting the phase-down of production and import of HFCs into Europe; and will not be affected by U.S. EPA SNAP regulations which would render it either unacceptable or acceptable subject to narrow use limits.

    F. Clean Agent must have a minimum safety factor 60% between the design concentration percentage and the No Observed Adverse Effect Level (NOAEL) for Class A and C hazards. For guidance on safety factors for Class B hazards, contact an approved Original Equipment Manufacturer.

    G. The minimum extinguishing concentration (MEC) determined by test as witnessed per recognized testing laboratory standards (i.e UL 2166, FM 5600) shall be no greater than 3.3%.

    H. Equipment shall be UL listed and FM approved and extinguishing agent shall be component recognized by UL or FM for use in the system.

    I. System cylinders shall be labeled indicating the system manufacturer and agent brand. System service and refill shall be by an authorized manufacturer’s representative and shall be the agent of the original installation brand.

    Download Complete Non-branded Specification Example (Word, 508 KB)
Copy and paste this text focused on environmental sustainability into your specification
Purple icon of the earth being wrapped with a leaf and stem, representing environmentally friendly

The fire suppression system shall include a 20-year warranty from the clean agent manufacturer that shall warrant the agent against any regulatory or phase down activity for a period of 20 years from the date of installation. The agent manufacturer shall supply a certificate to the end user indicating the date of the warranty and full terms and conditions.

  1. Summary of work

    A. Design, supply and install a complete clean agent total flooding fire suppression system using an environmentally sustainable clean agent.

  2. Clean Agent Fire Suppression Fluid

    A. Clean Agent shall have an Ozone Depletion Potential (ODP) of zero. ODP as defined by the US EPA.

    B. Clean Agent shall have a Global Warming Potential (GWP) of < 1 (100 year ITH.) GWP as defined by the Intergovernmental Panel on Climate Change Fifth Assessment Report (IPCC AR5) or in US EPA documentation and approvals.

    C. Clean Agent shall not be one of these greenhouse gases or ozone depleters; Perfluorocarbons (PFCs), Hydrofluorocarbons (HFCs), and Hydrochlorofluorcarbons (HCFCs).

    D. System cylinders shall be labeled indicating the system manufacturer and the agent. System shall be refilled with the original clean agent brand.

    E. Agents will not be restricted for use in fire protection due to its Ozone Depletion Potential (ODP) or Global Warming Potential (GWP) and is not targeted for phase-down by the Montreal Protocol, nor subject to the European F-Gas Regulations targeting the phase-down of production and import of HFCs into Europe; and will not be affected by U.S. EPA SNAP regulations which would render it either unacceptable or acceptable subject to narrow use limits.
Copy and paste this text focused on safety of occupants into your specification
Purple icon of people with a small heart on the front person

Clean Agent must have a minimum safety factor 60% between the design concentration percentage and the No Observed Adverse Effect Level (NOAEL) for Class A and C hazards. For guidance on safety factors for Class B hazards, contact an approved Original Equipment Manufacturer.

Copy and paste this text focused on noise concerns into your specification
Purple icon of data center with sound waves

The system shall be certified by the fire suppression system manufacturer to have a noise level during agent discharge not to exceed 110 dB, from 0.5 to 5.0 kHz, for longer than 20 seconds, at a distance of three feet from the gas discharge nozzle. The manufacturer shall supply certified testing documenting measured noise levels recorded by the LZFmax per 1/3 octave band center frequency, or other approved method.

Fire suppression system illustration with Novec 1230 cylinders